① The deviation between the measured values of air volume, fresh air volume, exhaust air volume, and return air volume at the air outlet and the design air volume shall not exceed 10%;
② The sum of air volume and return air volume should be approximately equal to the total supply air volume or the sum of all supply air volumes;
③ The total supply air volume should be slightly greater than the sum of the return air volume and exhaust air volume. The continuous operation of the ventilation system should not be less than 2 hours.
2. Testing of fresh air system
The fresh air system mainly consists of air ducts, fresh air regulating valves, and fresh air handling units. The testing method is the same as that of the air supply system. When adjusting the fresh air volume, it must meet the design requirements, otherwise various drawbacks may occur. If the fresh air volume is too high, it will increase the heat load of the refrigeration compressor and affect the indoor air conditioning effect; If the fresh air volume is too low, it does not meet the national hygiene standards and makes people feel stuffy and uncomfortable. Therefore, it is necessary to ensure the positive or negative pressure indoors and adjust the fresh air volume appropriately.
3. Debugging of air conditioning water system
The pipelines of the cold water system are long and complex, and the cleanliness requirements inside the system are high. Therefore, strict and careful cleaning is required when cleaning the pipes. Century Star recommends closing the inlet valves of fan coil units and other equipment before cleaning. Open the bypass valve to allow impurities inside the pipe during the cleaning process to be discharged outside the pipe through the bypass valve.
4. The normal joint trial operation of the air conditioning system with cold and heat sources shall not be less than 8 hours During the trial operation, various factors should be considered, such as whether the building decoration materials are dry and whether the indoor heat and humidity load meets the design conditions.
4、 Classification of air conditioning systems
1. Central air conditioning
All air handling equipment (fans, filters, heaters, coolers, humidifiers, dehumidifiers, refrigeration units, etc.) are centralized in the air conditioning room. After air treatment, they are sent to each air conditioning room through air ducts. This air conditioning system also has centralized heat and cold sources. It has a large air handling capacity, reliable operation, and is easy to manage and maintain, but the computer room occupies a large area.
2. Semi centralized air conditioning
The air treatment equipment concentrated in the air conditioning room only processes a portion of the air, and there are also air treatment equipment in scattered air conditioning rooms. They either process indoor air on-site or supplement and reprocess air from centralized processing equipment. Induction system, fan coil unit+fresh air system are typical examples of this semi centralized air conditioning system.
3. Local air conditioning
This system disperses all air handling equipment in air-conditioned rooms, hence the local air conditioning system is also known as a decentralized air conditioning system. The various air conditioners commonly used belong to this category. The air conditioner integrates indoor air handling equipment, indoor fans, and cold/heat sources and refrigerant output systems into a single box. Distributed air conditioning only delivers cold and hot carriers indoors, while the air is processed in the fan coil units inside the room.
Products center